Product name:Insulation Resistance tester 5KV
Item:BC2305
Details:


Overview

Digital Insulation resistance tester embedded real-time industrial microcomputer operating system, ultra-thin wire-shaped sheets header with the perfect combination of dot matrix liquid crystal display, the instrument is with a variety of voltage output level (500V, 1000V, 2500V, 5000V), high capacity, strong anti-interference, the pointer and digital synchronous display, AC-DC dual-use, simple operation, automatic calculation of various insulation index (absorption ratio, polarization index), all measured characteristics with the anti-power-down function . It is suitable for measuring high capacity transformers, transformers, generators, high voltage electric motors, power capacitors, power cables, surge arresters and other ideal insulation resistance test equipment.
 
Parameters:
1) Measuring range and accuracy
(Temperature, humidity:23±5℃, 45~75%RH)
 
Model
BC2305
Rated
Voltage
250V
500V
1000V
2500V
5000V
Measuring Range
0.099.9MΩ
100999MΩ
1.0010.0GΩ
0.099.9MΩ
100999MΩ
1.009.99GΩ
10.020.0GΩ
0.099.9MΩ
100999MΩ
1.009.99GΩ
10.040.0GΩ
0.099.9MΩ
100999MΩ
1.009.99GΩ
10.0100GΩ
0.099.9MΩ
100999MΩ
1.009.99GΩ
10.099.9GΩ
100200GΩ
Open circuit
Voltage
DC 250V
+20%, -0%
DC 500V
+20%, -0%
DC 1000V
+20%, -0%
DC 2500V
+20%, -0%
DC 5000V
+20%, -0%
Short-circuit
Current
Approx 3.3mA
Accuracy
±5%±3dgt
100GΩor more
±20%

2) Operating system:        Dual integration

3) Display:                                 Liquid crystal display(Max. 9999counts)
                                                 Bar graph / Max. 31points
4) Low battery warning:     Battery mark display (in 4 levels)
5) Over range indication:   “----“ mark appears on insulation resistance range.
6) Sample rate:                  approx 0.5~5 times/sec
7) Operable altitude:          2000m or less above sea level
8) Temperature & humidity range (guaranteed accuracy):
              23±5℃ / Relative humidity 85% or less (no condensation)
9) Operating temperature & humidity range:
              0℃~+40℃ / Relative humidity 85% or less (no condensation)
10) Storage temperature & humidity range:
              -20℃~+60℃ / Relative humidity 75% or less (no condensation)
11) Insulation resistance:   1000MΩ or more /DC 1000V
                                                 (Between electrical circuit and enclosure)
12) Dimension:           230(L) ×190(W) ×90(D) mm
13) Weight:                 approx 3.5kg (battery included)
14) Power source:             DC15V/4A Adapter Power
                                          Or DC9.6V: charging battery size AA×8pcs
[Next:BC2306]→