Product name:Secondary current injection
Item:JBC-703
Details:
Function
-Model 703 tester can simultaneously output standard six-phase current and six-phase voltage with 30A/phase current and 125V/phase voltage. Connecting six phase current in parallel can acquire 180A current. The tester can not only test traditional relays and protective devices, but also test modern microcomputer-based protective devices, especially the differential protection of transformers and automatic switching devices of stand-by power supply. Testing becomes more convenient and perfect.
-The main control board is of DSP+FPGA structure, outputting 16 bit DAC, which may generate 2000 points high density sine wave per week to fundamental wave, greatly ameliorate the quality of waveform and improve the accuracy of tester.
-The power amplifier is hi-fi linear type, which can both guarantee the precision of low current and the stability of heavy current.
-The device can directly access to PC machine through USB interface, needless of any patch cord.
-The device can run by access to notebook computer, which is installed with a same software, needless to relearn how to operate.
-The device has GPS synchronous testing function with embedded synchronization card (matching), which accesses to PC machine through RS232 interface, so the synchronous testing by exchanging two testers in different places can be achieved.
-The tester is equipped with independent special DC with auxiliary voltage source output, whose output voltages are 110V (1A), 220V (0.6A), for the purpose of meeting the power need of DC relay or protective devices.
-The tester has the function of auto-regulation by software, avoiding the calibration accuracy by opening cabinet to regulate potentiometer, so the stability of accuracy is greatly improved.
 
Parameters
         Item
         JBC-706 (6U 6I)
          JBC-703 (4U 3I)
 
 
 
 
 
 
 
AC-DC Voltage Source
Max Voltage
AC 6 x 125V DC6 x 150V
AC 4 x 125V DC 4 x 150V
Maximum Power
AC 6 x 75VA DC6 x 100VA
AC 4 x 75VA DC 4 x 100VA
Resolution
1mV
1mV
Accuracy
0.1%-0.2%
0.1%-0.2%
Frequency
Range0-1000HZ
Accuracy
0.001HZ
Range0-1000HZ
Accuracy
0.001HZ
Phase
Accuracy0.1 Degree
Accuracy0.1 Degree
Harmonic
Distortion
≤0.1%
≤0.1%
Other
Amplitude FrequencyPhase, separation of independent by phase, short circuitover loadingdistortionDistortion Protection,
4th Rd voltage can be set to zero-sequence voltage or arbitrary set
Amplitude FrequencyPhase, separation of independent by phase, short circuitover loadingdistortionDistortion Protection,
4th Rd voltage can be set to zero-sequence voltage or arbitrary set
 
 
 
 
 
 
AC-DC Current Source
Max Current
AC 6 x 30A    DC 6 x 20A
AC 3 x 40A    DC 3 x 20A
Maximum Power
AC 6 x 300VA DC 6 x 200VA
AC 3 x 300VA DC 3 x 200VA
Resolution
1mA
1mA
Accuracy
0.1%-0.2% Ultra-high-precision low current
0.1%-0.2% Ultra-high-precision low current
Frequency
Range0-1000HZ
Accuracy0.001HZ
Range0-1000HZ
Accuracy0.001HZ
Phase
Accuracy0.1 Degree
Accuracy0.1 Degree
Harmonic
Distortion
≤0.1%
≤0.1%
Other
Amplitude, frequency, phase, separation of independent by phase, short circuitover loadingdistortionDistortion Protection
Amplitude, frequency, phase, separation of independent by phase, short circuitover loadingdistortionDistortion Protection
Auxiliary DC voltage source
Output Voltage
DC110V/220V
DC110V/220V
Maximum Power
100W
100W
 
The Number Of Channel
8
7
 
Input Mode
Null InputDC5-250V0.5A
Null InputDC5-250V0.5A
 
Other
Dithered time can be set
Dithered time can be set
 
The Number Of Channel
4
4
 
Output Mode
DC 0-250V0.5A
DC 0-250V0.5A
Time Measurement
Range0.001-9.999.999S
Accuracy0.001S
Ran0.001-9.999.999S
Accuracy0.001S
Harmonic
2-20 times superposition harmonic of voltage and current wave can be set arbitrarily at the same time.
2-20 times superposition harmonic of voltage and current wave can be set arbitrarily at the same time.
Size
470mm x 405mm x 185mm
450mm x 400mm x 185mm
Weight
20 Kgs
16 kgs
Power
AC220V ± 10%50HZ ± 10%10A
AC220V ± 10%50HZ ± 10%10A
←[Previous:JBC-806] [Next:JBC-III]→